top of page
  • Air Velocity Sensor
  • Air Velocity Sensor
  • Air Velocity Sensor

Air Velocity Sensor

This device measures the actual velocity of the air, flowing through the duct. It is based on the principle of Single Point / Multipoint Pitot Tube for measuring Air velocity. It measures Air velocity by determining the difference between static and dynamic pressure. The Pitot Tube is constructed from SS304 material and thus immune to corrosive gases.

The velocity  varies according to the changes in density of the medium  due to changes in temperature and altitude of the installation location. The POLYGON  Precision Air Velocity Sensor comes with built-in RTD & special algorithm  for Temperature & Altitude compensation.

  • Power supply :

    24VDC

     

    Measuring Range :

    From 0-5 m/s to 0-40 m/s

    (Refer Selection Table)

     

    Signal Output :

    For FLP : 0-5V DC

    For Non FLP : 4-20mA or 0-10V DC

    (Refer Selection Table)

     

    ​​​​​​​Accuracy :

    ±3% FS. For Precision Models

    ±5% FS.For General Models

     

    Operating & Storage Ambient Conditions:

    -10 to 70˚C, 0 to 90%RH.

    Media temperature:

    15 to 35˚C (Model AVS 1XXX & AVS 2XXX)

    -10 to 100˚C (Model AVS 3XXX & AVS 4XXX)

     

    MOC :

    Pitot Tube :- SS 304

    Enclosure Head :-

    Non FLP – ABS

    FLP – LM6 Alloy

     

    Dimensions (Pitot Tube Length) :

    variable as per duct size (to be specified at the

    time of ordering)

     

    Protection:

    ABS Head : IP65 as per IS/IEC 60259-40050

    Flame Proof head : IP66 as per IS/IEC 60079-1: 2007, Gas Group I, IIA & IIB

     

Cut the queue. Get in touch to get in action.