Differential Pressure Transmitter with Certified FLP Enclosure
Differential Pressure Sensor cum Transmitter enclosed in an FLP enclosure, measures the differential pressure between any enclosed areas or with reference to the atmosphere. Some special applications of the sensor need a keypad for setting Low & high limits of the pressure, an audio-visual alarm and can optionally have a LED display .
It is of Wall mounted type. The FLP Enclosure is provided with 2 no.s of pressure ports and IP65 gland for cable entry.
Optionally, it can be provided with Modbus RTU connectivity to transmit the reading to the EMS/BMS Systems.
Supply Voltage:
24VDC
10V DC at 45mA (From Certified ZENER Barrier)
(ZENER Barrier not inclusive)
Sensor:
Basic sensing element – Programmable Electronic Chip.
Range:
-99 to 99 Pa.
0 to 99Pa
0 to 500Pa
0 to 1000 Pa
(Refer Selection Table)
Output Signal:
4-20mA
0-5V DC
(Refer Selection Table)
Accuracy:
±2% FS.
Communication: (Optional)
RS485 Modbus RTU.
Display: (Optional)
1” Red Seven segment display
Enclosure (Cabinet):
FLP Enclosure supplied with SS Nozzle & Cable Glands.
Construction as per IS/IEC 60079-1 2007
Area of Classification: Hazardous, Zone 1 & 2, Ex ‘d’
Protection: IP 65, as per IS/IEC 60529-2001
Atmosphere – suitable for Gas Gr. IIA & IIB
MOC: Cast Aluminum Alloy LM-6.
(Refer Selection Table)
Ambient Conditions for use as well as storage
Temperature: 0 to 75°C.
Humidity: 0 to 90 %RH Non-condensing